Skip to research

COMPONENT STUDY

Coolant distribution units and cold plates in AI racks

Follow the heat from cold plate to coolant distribution unit, compare in-rack and in-row designs, and see how acquisitions reshaped who makes them.

Pumps, a heat exchanger, filters and controls that circulate the rack’s clean coolant and pass its heat to the building’s water loop.

What does a CDU do?

Cold plates on the GPUs and CPUs carry heat into a technology cooling loop. The coolant distribution unit passes that heat through a liquid-to-liquid heat exchanger to the facility loop, keeps the two loops separate, and controls the rack loop’s pressure, flow and temperature with redundant pumps, filters and leak detection. NVIDIA’s GB200 NVL72 design calls for 120 kW of cooling per rack, and Lenovo’s GB300 NVL72 guide puts about 90% of the rack’s heat into liquid, with supply water as warm as 45 °C. NVIDIA says warmer water can reduce or eliminate the need for mechanical chillers in a wide range of climates.

In-rack, in-row or sidecar?

An in-rack CDU sits at the bottom of one rack and serves only that rack: Kaori’s takes the height of four 1U servers, Delta shows a 4RU 140 kW unit for GB300 NVL72, and Supermicro’s GB300 NVL72 rack carries one of up to 250 kW. In-row CDUs serve many racks from their own cabinet: Delta showed 2.4 MW and 3 MW liquid-to-liquid units in March 2026, Lite-On a 2.1 MW unit, Vertiv’s CoolChip range spans 70 to 2,300 kW, and Modine’s Airedale unit runs from 400 kW to more than 2 MW. Liquid-to-air sidecars, such as Supermicro’s 200 kW unit, suit sites without facility water. The illustrated rack shows an in-rack unit; Lenovo’s guide allows either placement.

Who makes cold plates and CDUs, and who owns them now?

Taiwanese and Chinese thermal specialists document AI liquid-cooling lines: AVC calls 2025 its “Inaugural Year of Liquid Cooling,” Auras shows cold plates, manifolds, quick disconnects and CDUs, Envicool and Delta sell cold plates and CDUs, and SUNON began shipping cold plates in 1H 2026. nVent says it defined a GB200 NVL72 reference architecture with NVIDIA using its CDUs, heat exchangers and manifolds. Industrial groups have acquired specialists: Eaton closed Boyd Thermal on Mar 12, 2026, Ecolab closed CoolIT on July 2, 2026, and Motivair and JetCool now sell as Motivair by Schneider Electric and a Flex company. Those units are reached only through their owners’ shares, and LiquidStack is private. Which supplier cools a given NVL72 rack is not disclosed.

How to research a liquid-cooling company

  1. Place the product in the loop: cold plate, manifold, quick disconnect, in-rack CDU, in-row CDU, sidecar or facility chiller. Each has different makers and scale.
  2. Compare ratings in the same unit: an in-rack CDU is rated in kilowatts for one rack, an in-row CDU in megawatts across many racks.
  3. Separate the evidence: a partner list, a claim of compliance with a reference design, a reference architecture and a named program are different milestones.
  4. Check ownership after the recent deals: Boyd Thermal (Eaton), CoolIT (Ecolab), Motivair (Schneider Electric), JetCool (Flex); AVC consolidates Fositek with a 16.87% holding.
  5. Check revenue mix and governance: servers were 66% of AVC’s Q2 2026 revenue, and Nidec’s shares were designated a Security on Special Alert after a Third-Party Committee reported inappropriate accounting.
  6. Use the list as a starting point: it is curated, not exhaustive, and the model is illustrative, not a bill of materials.

Sources

Engineering reference: Direct-to-chip liquid loop example. Company-specific evidence is linked from the profiles below.

Explore the complete liquid cooling sector · Read the mapping methodology

Related company research

These companies have relevant documented product roles. Open a profile for the source and limitation.

Also in this study (not publicly listed)

  • CoolIT Systems Subsidiary of Ecolab (ECL)

    Canadian maker of CDUs, cold plates, coldplate loops and rack manifolds, named by NVIDIA among Blackwell partners. Ecolab closed its ~$4.75 billion acquisition on July 2, 2026, so Ecolab (ECL) is the listed owner, proposed as a row.

    Source
  • Boyd Thermal Subsidiary of Eaton

    Cold plates, manifolds and CDUs for AI data centers; acquired by Eaton on Mar 12, 2026 for $9.55 billion net of cash. Boyd’s remaining Engineered Materials business is a separate private company.

    Source
  • Motivair Subsidiary of Schneider Electric

    Buffalo-based maker of CDUs, ChilledDoor rear-door heat exchangers and cold plates, now sold as Motivair by Schneider Electric; its exposure is through Schneider Electric’s row, not a separate stock.

    Source
  • JetCool Technologies Subsidiary of Flex (FLEX)

    “A Flex company”: SmartPlate cold plates (NVIDIA H100, RTX PRO 6000, Broadcom TH6), SmartSense in-rack CDUs, manifolds and quick disconnects.

    Source
  • LiquidStack Not publicly listed

    CDU maker (CDU-1MW; GigaModular CDU up to 14 MW) that says it is designed for AI factories including NVIDIA Vera Rubin and is “backed by” Trane Technologies’ manufacturing and service; whether Trane owns it was not verified, so Trane is not a stand-in.

    Source